Using Signals and Triggers in Tasker April 24, 2020

Signals and Triggers are very useful tools in the Tasker application. Signals are I/O values on either the JNIOR or a compatible expansion module with the JNIOR. Triggers are reactions to when a signal occurs. This post will explain all the parts of the Signal and Trigger tabs in detail.

The Signal Tab

To start, the Signal tab is needed in order to use the Triggers tab, so we’ll start with Signals. Signals are I/O values on either the JNIOR or a compatible expansion module with the JNIOR. Each Signal values has what device the Signal is coming from, the channel number of the value, and then the type of value its getting. These can be used either in a Trigger or to set/evaluate the value of a variable defined in a task.

The Trigger Tab

The Trigger is a reaction to a Signal value. Triggers are made up of first, a Trigger value that watches a Signal to react to, along with what the Signal value needs to be to activate the Trigger. Second, is the Reset value that monitors a Signal like the Trigger value does. The Reset value when activated resets the Trigger so it can activate again. A Trigger won’t activate after it has activated once already, unless the reset value activates. Lastly, a task name is selected as the task to run when the Trigger value is met and the Trigger activates.

These steps show show you how to properly create a Signal and Trigger.

Example

The example below will show you how to make a Trigger activate when Relay output 1 on the JNIOR goes High.

We’ll create two Signals with the first ones values being: Device is the Relay Output states of a JNIOR, the channel 1, and the type being the state. The second ones values would be: Device is the Relay Output states of a JNIOR, the channel 2, and the type being the state.

Afterwards you would begin configuring a Trigger. The Trigger values would be the Example Signal we created, and its trigger value will be high. For the Reset values, we’ll select the Example Signal Reset we created as the Reset value, and its reset value will be high as well. Lastly, we’ll pick whichever task we want to run during the Trigger activation as the Task value. In this example my task I created is Example Task.

By | On April 24, 2020 2:29 pm | No Comments | Categorized in: